250kW Gas/HVO/Oil Fired Packaged Boiler Plant
-
3030mm x 2438mm x 2599mm
-
3 tonnes (approx.)
Need Help?
01622 632 918
Specifications
Description
Environments
3D Tour
Specifications
- Maximum Output: 250kW Gas or Oil
- Boiler: Viessmann
- Burner: Oil
- Oil: Riello RL34
- Gas: RS34
- Pumps: Grundfos Magna 65-120 (duty/standby) variable drive
- Temperature Range: 60-90°C
- LTHW Connections: DN50
- Electrical: 32 amp 1 phase
- Gas Connection: 50mm
- Water Connection: 15mm
- Flow Rate: 4.86kg/s and 100kPA
- Dimensions (LxWxH): 3030mm x 2438mm x 2599mm
- Weight: 3 tonnes (approx.)
- Pressurisation Plant: 15mm manual main full
- Telemetry: Trend IQ3 controller with GSM modem reporting
- Variable Temperature: Yes
- Noise: 81 dBA
- Handling Options: HIAB
- HWS Connection: DN40
- HWS Flow Rate: 1Kg/s
- Max HWS Temperature: 60°C
- Maximum Static: 3Bar – max system volume 1500 litres (200 litre expansion vessel included)
- CWS Connection: DN40